| Indoor Air Quality Guide to Acceptable Conditions |
|
| INDOOR AIR QUALITY ACCEPTABLE CONDITIONS | | | TABLE 1. TYPICAL AND TRIGGER IAQ PARAMETERS | | | | |
|
| HUMAN MARKERS | | | TRIGGER CONDITIONS ** | | | | | TYPICAL CONDITIONS * | CONDITIONS* | |
| | |
| Comfort Issues | | 10% or less complaining of any one thermal condition | | | Greater percentages than these listed | |
| 20% or less complaining of general thermal conditions | |
| Health Issues | | Infectious diseases: 100% protected | | Any less than listed | |
| Asthma/allergies/MCS: 95-99% satisfied | |
|
| PHYSICAL MARKERS | | TYPICAL CONDITIONS* | | TRIGGER CONDITIONS** | |
| Temperature | | 68 degrees to 76 degrees Farenheit | | Temperatures outside this range. | |
| Temperature range in a space. | | 1-3 degrees Farenheit | | More than 3 degrees Farenheit | |
| Relative Humidity | | 40-60% RH | | <30% or >60% RH | |
| Building | | Under positive pressure; air delivered to occupied spaces | | Different conditions than listed | |
| Air movement on people | | Air velocities > 20fpm but x delivered to occupied spaces | | Different conditions than listed (80% satisfaction) | |
| Air velocities <100-200 fpm when warm | |
| Outdoor air delivery | | 20 cfm/person: offices | | Less than 15-20 | 15-20 cfm/person | |
| 15 cfm/person: classrooms | |
| Total air delivery to space | | 1 cfm/sq. ft; 6 air changes per hour (offices) | | Different conditions than listed | |
|
| CHEMICAL MARKERS | | TYPICAL CONDITIONS* | | | TRIGGER CONDITIONS** | |
| Carbon dioxide | | 400 to 1100 ppm | | 700+bkgrnd (ASHRAE 62-1999) | |
| TVOC | | 300 mg/m3 ( 1-2 ppm) | (approximately 1-2 ppm) | | Depends on compound; 300 mg/m 3 to 3000 mg/m 3 | |
| Formaldehyde | | 0.005 - 0.05 ppm | | >0.05 ppm (60 ug/m 3) | 60 mg/m 3 | |
| Carbon monoxide | | 1 - 3 ppm | | > 3 ppm | |
| NO2 | | 0.01 - 0.05 ppm | | 0.05 ppm | |
| Ozone | | 0.01 - 0.02 ppm | | > 0.02 ppm | |
| Particles | | up to 50 mg/m 3 (total) | | any visible aerosols (e.g., dust smoke); high quantities |
| up to 15 mg/m 3 (PM 2.5) | | of settled dust on flat surfaces; visible particles emitted |
| from supply registers | |
| Bioaerosols | | varies widely with site/locate | | Counts 2-3X greater than other spaces or outdoors | |
| Asbestos | | < 0.01 fb/cc | | > 0.01 fb/cc | |
| < 2 g/m 3 | |
| Radon | | < 0.5 pCi/lit | | > 4 pCi/lit (EPA recommended standard) | |
| Odors | | "none" | | Any detectable for extended periods of time | |
|
| * Non-industrial environments, e.g., office space, classroom, conference room. **Trigger means "take note," "investigate." | |
| Caution: Do not use the Table for compliance or design; always obtain competent professional assistance. Source: IAQ and HVAC Workbook, 2002, D. Jeff Burton. | |